Path: Top -> Journal -> Telkomnika -> 2019 -> Vol 17, No 6, Desember 2019
Mitigation of high voltage induction effect on ICCP system of gas Pipelines: a field case study
By : Rohana Ismail,Arnawan Hasibuan,Muzamir Isa,Faizar Abdurrahman,Nurul Islami, Telkomnika
Created : 2020-01-10, with 1 files
Keyword : ICCP, induction, mitigation, stransmission
Url : http://journal.uad.ac.id/index.php/TELKOMNIKA/issue/view/640
Document Source : web
An analysis of the high voltage induction effect on the impressed current cathodic protection
(ICCP) system on pipelines parallel toward high voltage power lines was employed in this research.
Mitigation of high voltage effect throught human and environment is necessary to implemented. Direct
current induction was used to increase the electrical potential of the gas pipeline, from Klumpang
to sicanang area, Indonesia. During the mitigation process, the highest induction value was obtained
0.00574 KV which is previously was 0.01732 KV, and occurred at the limit of the allowable secure touch
tension value of 0.015 KV. The data that acquire from the measurement of test point of ICCP underneath
the transmission line revealed a comparison data between field measurements occurred of mitigation
process. The direct current induction method is found to be safe for ICCP system and environment.
Keywords: ICCP, induction, mitigation, stransmissi
Property | Value |
---|---|
Publisher ID | gdlhub |
Organization | Telkomnika |
Contact Name | Herti Yani, S.Kom |
Address | Jln. Jenderal Sudirman |
City | Jambi |
Region | Jambi |
Country | Indonesia |
Phone | 0741-35095 |
Fax | 0741-35093 |
Administrator E-mail | elibrarystikom@gmail.com |
CKO E-mail | elibrarystikom@gmail.com |
Print ...
Contributor...
- , Editor: sukadi
Downnload...
Download for member only.
12493-36590-1-PB
File : 12493-36590-1-PB.pdf
(418323 bytes)