Study on Reactive Power and Harmonic Characteristics of DC Ice-melting Technology based on RTDS Simulation and Field Test
Study on Reactive Power and Harmonic Characteristics of DC Ice-melting Technology based on RTDS Simulation and Field Test
Journal from gdlhub / 2016-11-09 07:44:42Oleh : Lin Xu, Yang Han, Telkomnika
Dibuat : 2016-09-01, dengan 1 file
Keyword : DC de-icer, Real time digital simulator (RTDS), ice-melting current, deicing operation mode, harmonic and reactive power characteristics
Url : http://journal.uad.ac.id/index.php/TELKOMNIKA/article/view/3117
To study the characteristics of reactive power and harmonic of 500kV DC de-icer, the ice-melting technologies including the calculation method of critical ice-melting current, ice-melting time and maximum ice-melting current are clarified. The detail ice-melting methods and strategies for the 500kV transmission lines are proposed. Based on the ice-melting current calculation of Kang-Ding substation transmission lines in Sichuan, China, the 500kV/150MVA DC de-icer is deployed for the 500kV transmission lines. The effectiveness and feasibility of the ice-melting algorithm is validated by the RTDS simulation and the field test results. It is proved that the harmonic distortions of voltage and current are increased with the increasing ice melting current, which can be improved by the installation of passive filters.
Deskripsi Alternatif :To study the characteristics of reactive power and harmonic of 500kV DC de-icer, the ice-melting technologies including the calculation method of critical ice-melting current, ice-melting time and maximum ice-melting current are clarified. The detail ice-melting methods and strategies for the 500kV transmission lines are proposed. Based on the ice-melting current calculation of Kang-Ding substation transmission lines in Sichuan, China, the 500kV/150MVA DC de-icer is deployed for the 500kV transmission lines. The effectiveness and feasibility of the ice-melting algorithm is validated by the RTDS simulation and the field test results. It is proved that the harmonic distortions of voltage and current are increased with the increasing ice melting current, which can be improved by the installation of passive filters.
Beri Komentar ?#(0) | Bookmark
Properti | Nilai Properti |
---|---|
ID Publisher | gdlhub |
Organisasi | Telkomnika |
Nama Kontak | Herti Yani, S.Kom |
Alamat | Jln. Jenderal Sudirman |
Kota | Jambi |
Daerah | Jambi |
Negara | Indonesia |
Telepon | 0741-35095 |
Fax | 0741-35093 |
E-mail Administrator | elibrarystikom@gmail.com |
E-mail CKO | elibrarystikom@gmail.com |
Print ...
Kontributor...
- , Editor: sukadi
Download...
Download hanya untuk member.
3117-9130-1-PB
File : 3117-9130-1-PB.pdf
(1512541 bytes)