Path: Top -> Journal -> Telkomnika -> 2013 -> Vol 11, No 1: March

Electrical Tracking Formation on Silane Epoxy Resin under Various Contaminants

Electrical Tracking Formation on Silane Epoxy Resin under Various Contaminants

Journal from gdlhub / 2016-11-17 02:32:41
Oleh : Abdul Syakur, Hamzah Berahim, Tumiran Tumiran, Rochmadi Rochmadi, Telkomnika
Dibuat : 2013-03-01, dengan 1 file

Keyword : contaminant, epoxy resin, leakage current, electrical tracking
Url : http://journal.uad.ac.id/index.php/TELKOMNIKA/article/view/878

Kontaminasi pada permukaan isolator menjadi masalah serius. Khususnya untuk daerah tropis. Kelembaban dan hujan memainkan peranan yang penting dalam mengisi kebasahan permukaan isolator yang menghasilkan kontaminan dan arus bocor mengalir pada permukaan isolator. Arus bocor ini akan
membangkitkan panas yang terjadi pada permukaan isolator. Hal ini akan mengawali terjadinya lewat denyar. Makalah ini mempresentasikan pengaruh kontaminan terhadap arus bocor dan pembentukan jejak listrik pada permukaan sampel resin epoksi dicampur silicon rubber. Uji dilakukan berdasarkan metode Inclined Planed Tracking dengan kontaminan NH4Cl. Penggunaan kontaminan industri dan pantai untuk menjelaskan pengaruh kontaminan terhadap proses penjejakan permukaan. Laju aliran kontaminan 0.3 ml/menit. Tegangan 3.5 kV 50 Hz diterapkan ke elektroda atas. Ditemukan bahwa kontaminan industri menghasilkan arus bocor permukaan paling kecil 327.6 mA. Ditemukan kontaminan pantai menunjukkan kerusakan paling parah pada permukaan sampel. Oleh karena diperlukan perlakuan khusus pada sampel yang akan digunakan pada kondisi kontaminan tersebut agar unjuk kerja bahan dapat diperbaiki khususnya terhadap penjejakan listrik.

Deskripsi Alternatif :

Contamination at the surface of the insulator becomes a serious problem. Especially for the tropical area, humidity and rainfall play an important role in wetness by the water at the insulator surface, which result in the presence of contaminant and leakage current flowing at the surface. This leakage current will generate heat which occurs at the surface of an insulator. This ultimately leads to flashover. This paper presents the influence of contaminants to leakage current and formation of electrical tracking at the surface of epoxy resin compound wit silicon rubber. The test was based on IPT method with NH4Cl as contaminants. The industrial and coastal contaminants are used to explain the effect of contaminant at surface tracking process. The flow rate of contaminant was 0.3 ml/min. The 3.5 kV AC high voltage 50 Hz was applied to the top electrodes. It is found that industrial contamination resulting in the smallest surface leakage current is 327.6 mA. Also it is found that coastal contaminant showed the severest damage at surface of test sample. Therefore, special treatment of the sample is needed under these conditions so that the material performance can be improved, especially against the electrical tracking.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID Publishergdlhub
OrganisasiTelkomnika
Nama KontakHerti Yani, S.Kom
AlamatJln. Jenderal Sudirman
KotaJambi
DaerahJambi
NegaraIndonesia
Telepon0741-35095
Fax0741-35093
E-mail Administratorelibrarystikom@gmail.com
E-mail CKOelibrarystikom@gmail.com

Print ...

Kontributor...

  • , Editor: sukadi

Download...

  • Download hanya untuk member.

    878-1408-1-SM
    Download Image
    File : 878-1408-1-SM.pdf

    (476222 bytes)